YH-TS600HP is a touchscreen-based leak alarm receiver designed to manage leak detection systems clearly and efficiently on site. Operators can view leak status and alarm history at a glance, while Ethernet communication enables real-time data transmission to an external server (central monitoring), making it ideal for building a monitoring platform. It supports efficient operation in environments requiring multi-channel leak safety management such as smart factories, large plants, laboratories, and production lines.


● Touchscreen Leak Monitoring UI: Visualizes leak detection status on-screen to shorten on-site response time.
● Real-Time Server Transmission (Ethernet): Sends leak alarm/status data to an external server for central monitoring and event history management.
● Scalable Integration for Field Applications: Supports signal interfacing and communication settings to build a reliable leak safety monitoring system across different facility environments.
| Item | Specification |
| Model | YH-TS600HP (Touchscreen Leak Monitoring Alarm Receiver) |
| Power Supply | AC 220V 60Hz |
| Power Consumption | Max 30W |
| Main Power Indicator | Yellow lamp ON (Power ON) |
| Backup Power Indicator | Red lamp ON |
| Display | Touch Screen Display |
| Operating Temp./Humidity | -10–40°C, 0–80% RH |
| Buzzer | 70dB or higher (at 1m distance) |
| Backup Power | Ni-Cd battery DC 24V (Option) |
| Alarm Output | Relay contact COM/NO, Ethernet transmission |
| Recommended Cable | VCT or CVVS, 0.75mm² or higher |
| Channels | • Leak detectors: 1–20 CH • Multi-zone leak status visualization/management via touchscreen |
| Key Functions | • Leak monitoring: visual display of leak detection status on touchscreen • User-friendly operation: easy setup and status checks by touch • Integration protocol support for connecting with other systems • Server transmission: real-time leak data transfer via Ethernet • Central monitoring: provides real-time status data to a central system • Adjustable transmission interval via touchscreen • Options: RS-232/485, Modbus, 4–20mA output, individual contacts |
♣ Dimensions may vary depending on explosion-proof and warning light options.